KVH Tokyo Data Center 1 (TDC1)

Premium colocation and access to a rich financial ecosystem

KVH Tokyo Data Center 1 (TDC1) is the ideal managed hosting environment for high frequency trading participants wishing to colocate close to the Japanese exchanges. Recommended by the Tokyo Stock Exchange, Tokyo Commodities Exchange, Tokyo Financial Exchange, and Osaka Securities Exchange as an official access point and proximity hosting provider, KVH TDC1 provides tenants with an optimal low latency environment. It also offers 7,600m² of compute space within Tier III+ architecture.

Key Features

Purpose-Built for Financial Customers

  • Close physical proximity to all major Japanese exchanges
  • An ideal location for making the fastest connections to exchanges and a full financial ecosystem of HFT participants, already on-net and only a cross-connect away

Carrier Neutral

  • Flexibility to choose from a variety of carriers

Power

  • True 2(N+1) power redundancy
  • Two 66kV closed loop receiving system from TEPCO
  • Power capacity:
    2F, 3F and 7F: Average power capacity: 750w / m², Max power: 1,500w / m²
    4F and 5F: Average power capacity: 850w / m², Max power: 1,700w / m²

Security

  • Compliance with international and Japanese ISMS and SAS70 standards
  • Multilayer physical security with biometric authentication systems and mantraps on each floor
  • Security personnel on-site 24×7

Support

  • Bilingual Service Desk (English and Japanese) and customizable Smart Hands services to act as your eyes, hands, and feet, 24x7x365

Building and Operation

Construction
  • Reinforced Concrete Construction: B1F, Steel construction: 1F-8F
  • Anti-seismic construction designed to withstand up to an intensity 6 earthquake on the Japanese (JMA) scale
Space
  • DC-5 Floors: 7,950m² for racks
Connectivity
  • High-performance connectivity using KVH’s resilient, low-latency backbone
  • Multi-carrier connectivity also available
Management and Monitoring
  • Bilingual operations staff on-site 24×7
  • Active monitoring and maintenance of all equipment

Power and UPS

Power to site
  • Two 66kV closed loop receiving system from TEPCO
Power capacity
  • 2F, 3F and 7F: Average power capacity: 750w / m², Max power: 1,500w / m²
  • 4F and 5F: Average power capacity: 850w / m², Max power: 1,700w / m²
UPS
  • 2 (N+1) configuration
  • 10-minute UPS autonomy under full load
Standby Generators
  • N + 1 configuration, gas turbine
  • Minimum 48 hours of operability under full load without refueling. Guaranteed refueling adds 24 hours. Repeated refueling allows for continuous operability.

Cooling

Cooling
  • N + 1 Computer Room Air Conditioning (CRAC) units, each with dual refrigeration compressors for accurate cooling capacity over the entire raised floor
  • Fully looped condenser water cooling system on the roof provides dual path water feeds to the computer room air-conditioners
Leak Prevention
  • Water leak sensors are installed on pipes and CRACs, and each CRAC has watertight edges and drains installed in front of it
Cooling Controls
  • Precise temperature and controlled humidity within a pre-set range
  • Temperature setting is 22 ± 2℃, Humidity setting is 45 ± 5% RH

Safety

Fire Suppression
  • IT space is protected by an inert gas-based fire suppression system
  • Fire hydrants and extinguishers are installed in the ancillary areas
Smoke Detection
  • VESDA early warning system
  • High-sensitivity heat and smoke detectors
Staffing
  • Security personnel on-site 24×7
Access Controls
  • Multi-layer physical security with biometric authentication system
  • Mantraps are located on each floor to prevent unauthorized access – the second door will not open, until the first door is closed.
  • *1 Colocation and wholesale services from TDC1 and TDC2
  • *2 TDC1 and TDC2 follow FISC Security guidelines on Computer Systems for Banking and Related Financial